Specifications:

R410A Water Cooled Floor Standing Air Conditioners
Model:PWC-K525CM
Capacity:52.5 kW
Power Supply:3ph, 220V, 60Hz
R22 Scroll

Water Cooled Floor Standing Air Conditioners

Applications :

 

This packaged type air conditioner can be used widely in hotels, apartments, restaurants, office buildings, shopping malls, supermarkets, hospitals, gymnasiums, factories and so on.

 

Features :

  • High-efficiency.
  • Anticorrosive paint .
  • Free blow type or ducted type optional.

Specifications :

Model

PWC-K525CM

Duct Type (Free Blow Type Optional)

Cooling Capacity    (Remark 2) 

kW

52.5

Power Supply

 

3ph, 220Vac, 60Hz

Electric CharacteristicsTotal Power Consumption

kW

12.35

Total Current

A

39.0

Starting Current

A

197

E.E.R.

(W/W)

4.25 

Compressor Type 

Scroll

Quantity 

2

Power Output

kW

5.2

Crankcase Heater

W

-

BlowerFan Quantity 

2

Air Flow Rate

m3/min

130

Extenal Static Pressure

Pa

80

Power Output

kW

2.2

Protection Devices    (Remark 4) 

 

a, b, c, d, e

Cooling Water (30oC)Water Flow Rate

m3/hr

11.3

Head Loss

kPa

24.5

Pipe SizeCooling Water Outlet/Inlet

B

2

Drain (condenser)

B

1

Drain (mechanic chamber)

B

1

DimensionsHeight

mm

1875

Width

mm

1549

Depth

mm

630

Plenum Height

mm

+280

Net Weight

kg

420

Remarks :

1. The electric power supply must be in compliant with this table for each model. Any damage or failure caused by using power supply other than specified in this table is not covered in the warranty.

2. The cooling capacity is tested under the conditions specified in ISO.

Operation conditions:Indoor side intake air temperature 27oC, wet bulb temperature 19oC; intake cooling water temperature 30oC, and outlet temperature 35oC.

3. Suitable temperature range : 21oC~ 30oC.

4. Mark of Protection devices : a:High-low pressure switch, b:thermal overload, c:compressor internal thermostat, d:de-ice protector, e:phase protector.

5. To modify the ducted type packaged air conditioner to the free blow type; you need to buy the plenum in addition.

6. For the continuous development, the specifications are subjected to modification without notice.

7. If you have any special requirment, please inform us before placing order.

Please contact us for details.

Contact us
Company Name: TECO Electric & Machinery Co., Ltd.  
Company Address: 10F, No. 3-1, Yuan Cyu St., Nan-Kang 
Zip: 115 
Contact Person: Ms. Cindy Lo 